Rectangular fire damper CU2-L500
Wide-ranging rectangular fire damper up to 120’
CU2 rectangular fire damper with a tunnel casing extension at the wall side. This extension of our rectangular fire damper is used to facilitate the connection to the duct when the supporting construction is thicker than 100 mm.
Available dimensions (Hn/Wn): 200×200 mm > 1500x1000mm
Components:
|
Features:
- Hygiene certificate (www.HYG.de) for CU2: H > 600 or W > 800
- Tested according to EN 1366-2 up to 500 Pa
- Suitable for built-in installation
- Minimal distance allowed for this type of rectangular fire damper
- Rectangular fire damper suitable for rigid wall, rigid floor and light wall (metal stud gypsum plasterboard wall, gypsum blocks)
- Sealing with fire resistant stone wool boards allowed, also for asymmetric opening
- Air tightness in accordance with EN 1751: class B (class C in option )
- Operating mechanism of the rectangular fire damper is outside the wall
- Maintenance-free
- For indoor use
- Operating temperature: max. 50°C
- Intermediate dimensions on request
Mechanisms:
Download Technical datasheet KIT
The unlocking mechanism CFTH automatically unlatches the damper blade when the temperature in the duct rises above 72°C. The damper can also be unlocked and reset manually. |
VARIANTS
- CFTH
Mechanism with fusible link
OPTIONS – SWITCH
- FCU
Limit switch ‘open/closed’ - FDCU
Unipolar limit switch ‘open/closed’ - FDCB
Bipolar auxiliary limit switch ‘open/closed’
UNLOCKING
- manual unlocking
press the unlocking button (1). - automatic unlocking
the fusible link melts when the temperature reaches 72°C in the duct. - remote unlocking
n/a
RESETTING
- manual resetting
Use the enclosed Hex key and turn clockwise(2) - motorised resetting
n/a
Download Technical datasheet KIT
VARIANTS
- ONE T 24 FDCU ST
Spring return actuator ONE 24V (with fusible link) + unipolar beginning- and end-of-range switch and plug (ST) - ONE T 24 FDCU
Spring return actuator ONE 24V (with fusible link) + unipolar beginning- and end-of-range switch - ONE T 230 FDCU ST
Spring return actuator ONE 230V (with fusible link) + unipolar beginning- and end-of-range switch + plug (ST) - ONE T 230 FDCU
Spring return actuator ONE 230V (with fusible link) + unipolar beginning- and end-of-range switch - ONE T 24 FDCB
Spring return actuator ONE 24V (with fusible link) + bipolar beginning- and end-of-range switch - ONE T 230 FDCB
Spring return actuator ONE 230V (with fusible link) + bipolar beginning- and end-of-range switch
UNLOCKING
- manual unlocking
shortly press the unlocking button (1) once. - automatic unlocking
the fusible link reacts as soon as the temperature in the duct reaches 72°C. - remote unlocking
by interrupting the power supply.
RESETTING
- manual resetting
open the battery compartment (4) and press a 9V battery against the contact springs. Hold this position until the LED (3) emits a continuous light. Check whether the indicator (2) shows that the damper blade is in the open position. Remove the battery, the LED fades away. Close the battery compartment. - motorised resetting
switch off the power supply for at least 5 sec. Power the actuator (respect the prescribed voltage) for at least 75 sec. The resetting stops automatically when the end of range is reached (damper open).
Download Technical datasheet KIT
The ONE-X is a spring return actuator with integrated communication module designed to simply operate Rf-t fire dampers of all sizes, automatically or remotely. The ONE-X is available in two versions: 24 V and 230 V.
|
VARIANTS
- ONE-X 24
Spring return actuator ONE-X 24V (with fusible link T) with integrated communication module - ONE-X 230
Spring return actuator ONE-X 230V (with fusible link T) with integrated communication module
UNLOCKING
- manual unlocking
shortly press the unlocking button (1) once. - automatic unlocking
the fusible link reacts as soon as the temperature in the duct reaches 72°C. - remote unlocking
via ZENiX controller
RESETTING
- manual resetting
Open the battery compartment (4) and press a 9V battery against the contact springs. Hold this position until the red LED (3) emits a continuous light. Control whether the indicator (2) indicates that the damper blade is open. Remove the battery. Close the battery compartment. - motorised resetting
via ZENiX controller. By applying voltage during first use.
Download Technical datasheet KIT
VARIANTS
- BFL24
Spring return actuator BFL 24V - BFL24-ST
Spring return actuator BFL 24V with plug (ST) - BFL230
Spring return actuator BFL 230V - BFLT24
Spring return actuator BFL 24 V with thermo-electric fuse (T) - BFLT24-ST
Spring return actuator BFL 24 V with thermo-electric fuse (T) and plug (ST) - BFLT230
Spring return actuator BFL 230 V with thermo-electric fuse (T) - BFLT230-ST
Spring return actuator BFL 230 V with thermo-electric fuse (T)
OPTIONS – SWITCH
- SN2 BFL/BFN
Auxiliary limit switch ‘open/closed’
UNLOCKING
- manual unlocking
place the locking button on “unlock”. (In case of BFLT: the damper can alternatively be unlocked by pushing the “test” button on the thermo-electric fuse) - automatic unlocking
the thermo-electric fuse reacts as soon as the temperature reaches 72°C (type BFLT). - remote unlocking
by interrupting the power supply.
RESETTING
- manual resetting
turn the enclosed handle anti-clockwise. To block the motor, place the locking button on “lock” - motorised resetting
switch off the power supply for at least 10 seconds. Supply the actuator (respect the prescribed voltage) for at least 75 seconds. The resetting stops automatically when the end of range is reached (damper open) – it takes about 60 seconds to reset the damper – or when the power supply is interrupted.
Download Technical datasheet KIT
VARIANTS
- BFN24
Spring return actuator BFN 24V - BFN24-ST
Spring return actuator BFN 24V with plug (ST) - BFN230
Spring return actuator BFN 230V - BFNT24
Spring return actuator BFN 24 V with thermo-electric fuse (T) - BFNT24-ST
Spring return actuator BFN 24 V with thermo-electric fuse (T) and plug (ST) - BFNT230
Spring return actuator BFN 230 V with thermo-electric fuse (T)
OPTIONS – SWITCH
- SN2 BFL/BFN
Auxiliary limit switch ‘open/closed’
UNLOCKING
- manual unlocking
place the locking button on “unlock”. (In case of BFNT: the damper can alternatively be unlocked by pushing the “test” button on the thermo-electric fuse) - automatic unlocking
the thermo-electric fuse reacts as soon as the temperature reaches 72°C (type BFNT). - remote unlocking
by interrupting the power supply.
RESETTING
- manual resetting
turn the enclosed handle anti-clockwise. To block the motor, place the locking button on “lock” - motorised resetting
switch off the power supply for at least 10 seconds. Supply the actuator (respect the prescribed voltage) for at least 75 seconds. The resetting stops automatically when the end of range is reached (damper open) – it takes about 60 seconds to reset the damper – or when the power supply is interrupted.
Download the technical brochure of the CU2 series
Dear,
Thank you for expressing interest in our products. We are delighted to provide you with the technical brochure of the CU2 series. We appreciate your enthusiasm and look forward to assisting you further on your journey.
To download the brochure, please click the button below:
We hope that our product brochure provides you with comprehensive insights into the features and benefits of the CU2 series. If you have any questions or require additional information, please don’t hesitate to reach out to our friendly sales & support team.
Thank you again for choosing Rf-Technologies.
Best regards,
Tony Readdy
Technical Sales Expert UK
M. 07939 316006 | tony.readdy@rft.eu